INSTALLER/OWNER RESPONSIBILITY
Beautiful hardwood floors are a product of nature and
therefore, not perfect. Our wood floors are manufactured in accordance with
accepted industry standards, which permit a defect tolerance not to exceed 5%.
The defects may be of a manufacturing or natural type.
- The installer assumes all responsibility for final inspection of product
quality. This inspection of all flooring should be done before installation.
Carefully examine flooring for color, finish and quality before installing
it. If material is not acceptable, do not install it and contact the
seller immediately.
- Prior to installation of any hardwood-flooring product, the installer
must determine that the job-site environment and the sub-surfaces involved
meet or exceed all applicable standards and recommendations of the construction
and materials industries. These instructions recommend that the construction
and subfloor be dry, stiff and flat. The manufacturer declines any responsibility
for job failure resulting from or associated with sub-surface or job-site
environment deficiencies.
- Prior to installation, the installer/owner has final inspection responsibility
as to grade, manufacture and factory finish. The installer must use
reasonable selectivity and hold out or cut off pieces with defects,
whatever the cause.
- Use of stain, filler or putty stick for defect correction during installation
should be accepted as normal procedure.
- When flooring is ordered, 5% must be added to the actual square footage
needed for cutting and grading allowance.
- Should an individual piece be doubtful as to grade, manufacture or
factory finish, the installer should not use the piece.
- Use of appropriate products for correcting subfloor voids should be
accepted as a normal industry practice.
TOOLS & ACCESSORIES NEEDED
- Broom
- Robbins Acrylic Filler
- Tape Measure
- Hammer
- Chalk line & chalk
- Recommended Adhesives (SoundSeal Joint Adhesive & ProConnectTM
or FusionLock Hardwood Flooring Adhesive) & Adhesive Cleaner
- Hand saw or jamb saw
- Robbins ForEver II Hardwood Flooring Cleaner
- Electric power saw
- Recommended trowel
- Moisture meter (wood, concrete or both)
- Safety glasses
- Square
- 8-penny nails
- Installation bar
- Wedges
- Tapping Block (floating)
- Tapping Block (glue-down)
- 3M 2090 Blue Mask Tape
PRE-INSTALLATION PROCEDURES
Job Site Inspection
- The building should be closed in with all outside doors and windows in place.
All concrete, masonry, framing members, drywall, paint and other "wet"
work should be thoroughly dry.
- The wall coverings should be in place and the painting completed except
for the final coat on the base molding. When possible, delay installation
of base molding until flooring installation is complete.
- Exterior grading should be complete with surface drainage directing
water away from the building. All gutters and downspouts should be in
place.
- Floating floors may be installed on, above or below grade level. Do not
install in full bathrooms.

- Basements and crawl spaces must be dry and well ventilated.
- Crawl space must be a minimum of 24" (600 mm) from the ground
to underside of joists. A ground cover of 6-8 mil black polyethylene
film is essential as a vapor barrier with joints lapped six inches and
taped. The crawl space should have perimeter venting equal to a minimum
of 1.5% of the crawl space square footage. These vents should be properly
located to foster cross ventilation (see figure #1).

- Subfloor must be checked for moisture content using the appropriate testing
method.
- Permanent air conditioning and heating systems should be in place and
operational. The installation site should have a consistent room temperature
of 60-75° F and humidity of 35-55% for 14 days prior, during and until
occupied, to allow for proper acclimation.
STORAGE AND HANDLING
Handle and unload with care. Store in a dry place being sure to provide at
least a four-inch air space under cartons which are stored upon
"on-grade" concrete floors. Flooring should not be delivered until the
building has been closed in with windows and doors in place and until cement
work, plastering and all other "wet" work is completed and dry.
Concrete should be at least 60 days old. Floating floors should be stored in the
environment in which it is expected to perform. Air conditioning/heating systems
should be in place and in operation at least 14 days prior, during and after
installation of the flooring. Do not open the packages until you are ready to
install. Humidity may cause the tongue to swell on opened packages making
installation difficult. Check adhesive label for storage limitations.
INSTALLATION APPLICATIONS
FLOATING INSTALLATION
- Use PolyCushion floating floor underlayment (shown in header on page 1).
- Use SoundSeal joint adhesive (shown in header on page 1).
GLUE-DOWN INSTALLATION
- Use recommended trowel (figure #2) to get required spread rate and ridging
height.
- Use SoundSeal joint adhesive and ProConnectTM or FusionLock
hardwood flooring adhesive (shown in header on page 1).

SUBFLOOR REQUIREMENTS
SUBFLOORS MUST BE:
- CLEAN - Scrape, broom clean, and smooth. Free of wax, paint, oil, sealers,
adhesives, curing agents and other debris.
- LEVEL/FLAT - Within 3/16" in 10' and/or 1/8" in 6'. Sand
high areas or joints. If the floor is to be glued down, fill low areas
(no more than 1/8" at a time) with a cementitous leveling compound
or milk additive latex patch of 3,000-PSI minimum compressive strength.
Follow the instructions of the leveling compound manufacturer. Leveling
compounds must be tested for moisture to ensure they are properly cured
and within the manufacturer's specified requirements for proper installation.
- STRUCTURALLY SOUND - Nail or screw any loose areas that squeak. Replace
any water-damaged, swollen or delaminated subflooring or underlayments.
Avoid subfloor with excessive vertical movement unless they have been
properly stiffened prior to the installation of the wood flooring.
- DRY - Check moisture content of the subfloor with a reliable moisture
meter.
RECOMMENDED SUBFLOOR SURFACES
- PREFERRED: 3/4" (19 mm) CDX grade plywood
- 3/4" chip, waferboard, particleboard
- 3/4" (23/32") OSB PS2 rated underlayment
- MINIMUM: 5/8" CDX grade plywood
- Radiant heated subfloors
- Acoustic concrete
- Existing solid wood flooring
- Ceramic, terrazzo, slate and marble
- Vinyl, resilient tile, cork flooring
- Metal
- Concrete slabs
- Cork (Acoustic)
CONCRETE SLABS
Floating floors can be glued directly to concrete or floated over them. In
glue-down applications, do not use a concrete sealer nor install over one.
Surface preparation using mechanical methods such as sanding or scouring with
open coat paper or a titanium disk is preferred. The concrete must be of high
compressive strength. All concrete subfloors should be tested for moisture
content. Visual checks are not reliable. Acceptable test methods for subfloor
moisture content include:
NOTE: Test several areas, especially near exterior walls and
walls containing plumbing.
- A 3% Phenolphthalein in Anhydrous alcohol solution. Chip the concrete at
least ¼" deep (do not apply directly to the concrete surface) and
apply several drops of the solution to the chipped area. If any color
change occurs, further testing is required.
- Calcium Chloride test. The maximum moisture transfer must not exceed
3 lbs./1000 square feet with this test.
- Tramex Concrete Moisture Encounter meter (figure #3). Moisture readings
should not exceed 4.5 on the upper scale. (Figure #3 shows an unacceptable
reading of over 4.5)

A "DRY" SLAB, AS DEFINED BY THESE TESTS CAN BE WET AT OTHER TIMES
OF THE YEAR. THESE TESTS DO NOT GUARANTEE A DRY SLAB. ALL CONCRETE SLABS SHOULD
HAVE A MINIMUM OF 6 MIL POLY FILM MOISTURE BARRIER BETWEEN THE GROUND AND THE
CONCRETE.
Moisture Barrier System: If moisture is present, inexpensive sheet vinyl or
"slip-sheet" (PVC) may be installed. Use a premium grade, alkaline
resistant adhesive and a full spread application system to properly bond the
vinyl to the subfloor. Follow the sheet vinyl manufacturer instructions for
installation procedures. A patch test may be required as an adhesion test.
Install several small areas (3' x 3') and allow the vinyl to set for 72 hours.
Remove the vinyl; if the backing remains attached to the concrete, the subfloor
should be acceptable for sheet vinyl installation. If you have any questions
regarding installation or the handling of moisture problems, please contact the
distributor/retailer from whom the goods were purchased.
ACOUSTIC CONCRETE
Acoustic concrete normally contains large quantities of gypsum that may
inhibit the adhesive's capability to properly bond. For glue-down applications,
acoustic concrete must be primed with the concrete manufacturers recommended
primer/surface hardener.
WOOD SUBFLOORS & WOOD STRUCTURAL PANEL SUBFLOORS
- Plywood: Must be APA grade rated sheathing or CDX minimum.
- Oriented Strand Board (OSB): Must be PS2 rated installed
sealed side down.x Particleboard must be a minimum 40-LB density, stamped
underlayment grade and ¾" thick.
Make sure existing floor or subfloor is dry and well nailed or screwed down
every 6" along each joist to avoid squeaking or popping before the floor is
installed. The wood subfloor must not exceed 13% moisture content. Measure
moisture content of both subfloor and wood flooring to determine proper moisture
content with a reliable wood moisture meter. The difference between the moisture
content of the wood subfloor and the wood flooring must not exceed 4%.
Optimum performance of hardwood floor covering products occurs when there is
no horizontal or vertical movement of the subfloor. The MINIMUM subfloor
recommendations described above for 16" O/C joist spacing. The thicker,
PREFERRED subfloor recommendations described above will allow 19.2" O/C
joist spacing if the joist manufacturer's recommended span is not exceeded.
Spacing in excess of 19.2" O/C does not offer optimum results. Install
flooring perpendicular to the floor joists when possible. Installations should
not be made parallel to the floor joists or on joist spacing that exceeds
19.2" O/C unless the subfloor has been properly stiffened. Stiffening may
require the addition of a second layer of subflooring material to bring the
overall thickness to at least 1-1/8".
All underlayment panels should be spaced 1/8" apart to insure adequate
expansion space. This can be achieved by using a circular saw set at the depth
of the underlayment and cutting around the perimeter of the panel. T&G
panels normally have built in expansion; DO NOT cut around the perimeter of
T&G panels. Do not install over existing glue-down wood floors. Do not
install over nailed floors that exceed 3-¼" in width. Wide width floors
must be overlaid with plywood. When installing over existing wood floors
parallel with the flooring, it may be necessary to install an additional ¼"
layer of plywood to stabilize the flooring or install the wood floor at right
angles. Applicable standards and recommendations of the construction and
materials industries must be met or exceeded.
RESILIENT TILE, RESILIENT SHEET VINYL & CORK FLOORING
If the tiles or sheet goods are well bonded, the flooring can be glued
directly to the surface. Clean the surface thoroughly with a good quality
household detergent. De-gloss flooring as necessary to create a good adhesive
bond using an abrasive pad. If vinyl appears to have a coating of wax or other
maintenance materials, it must be removed with the appropriate floor stripper.
Allow ample drying time. (NOTE: Do not sand any resilient
products for they may contain asbestos fibers, which may be harmful.) Do not
direct glue to floors that exceed two layers; install as a floating system only
under these circumstances. Cork floors must have all sealers and surface
treatments removed before installation begins if a direct glue-down application
is preferred.
CERAMIC, TERRAZZO, SLATE & MARBLE
All grout joints and broken corners that exceed 1" must be filled
with a cementitous leveling compound mixed with Latex additive of a glue-down
application is preferred. The surface should be cleaned and abraded to create a
good bonding surface for the adhesive. Loose tiles must be re-adhered to the
subfloor or filled as above for both glue-down and floated applications.
CORK (ACOUSTIC)
Floating floors can be glued or floated directly over full-spread,
permanently bonded acoustic cork. The cork should have a density of no less than
11.4 lb./cubic foot and no more than 13 lb./cubic foot. The cork, in general,
should be pure cork combined with a polyurethane binder. Cork thickness is to be
no more than ¼" (6 mm). Install cork in accordance with manufacturer's
recommendations. DO NOT use cushion underlayment when floating over these
surfaces.
SUBFLOORS WITH RADIANT HEAT
- System must be operational and heated for at least 7 days prior to beginning
installation.
- Turn off heat and let subfloor cool down to room temperature 3-4 hours
prior to starting the job.
- Radiant heated floors must be temperature controlled or engineered
for the R-rating of the floor-covering product installed upon them.
BEFORE installation begins, ascertain that the system is designed and
controlled for wood flooring. Failure to do so may cause excessive heat
damage, shrinkage and delamination.
- After installation, turn system back on immediately to its normal room
temperature setting. The subfloor surface must not exceed 85° F throughout
the life of the floor.
DOORWAY AND WALL PREPARATION
Undercut door casings. Remove any existing base, shoe mold or doorway
thresholds. These items can be replaced after installation. All door casings
should be notched out (figure #4) or undercut to avoid difficult scribe cuts.
GENERAL INSTALLATION TIPS
- Floor should be installed from several cartons at the same time to ensure
good color and shade mixture.
- Be attentive to staggering the ends of boards in adjacent rows at
least 16" when possible (figure #5). This will help ensure a more
favorable overall appearance of the floor.

- DO install from closed/sealed cartons. DO NOT remove materials from their
sealed container prior to installation.
- DO tighten panels by tapping against the recommended tapping block
with a hammer. DO NOT tighten panels by striking directly with the tapping
block or a hammer.
- DO glue all joints with SoundSeal when using a floating system. The
glue MUST be applied to the top of the tongue, DO NOT apply adhesive
in the groove
- DO use a starter board that is adequately fastened to a straight starting
line.
- DO use PolyCushion underlayment on all floating floors over subfloors
that require it.
- DO Not use short tapping blocks that can damage the edge. Do Not use
lightweight wooden tapping blocks. Do Not use grooved tapping blocks.
- DO NOT use laminate straps to tighten the flooring panels.
STEP 1: ESTABLISH A STARTING POINT
- Installation parallel to the longest wall is recommended for best visual
effects, however, the floor should be installed perpendicular to the
flooring joists unless subfloor has been reinforced to reduce subfloor
sagging. Find appropriate subfloor from "Subfloor Type" section
in this instruction manual.
- When possible, always begin layout or installation from an outside
wall, as these are normally the straightest.
- Pre-plan the floor by counting the number of planks (in width) that
it will take to complete the floor. Avoid finishing out with a rip narrower
than 2". Plan to start the first row with a partial board, ripping
it to the necessary width to avoid a narrow rip on the final wall.
- In at least two places 12"-16" from the corner, measure out
equal distance from the starting wall (figure #6)

and snap a chalk line. The chalk should be of a bright color so that it is
visible through the underlayment or adhesive. If a partial, ripped board is
required (as above) it can be installed after the balance of the flooring has
been completed. Adjust the starting line to allow for the width of the board
plus ½" for expansion. Ascertain that the wall is straight. If it is not,
scribe the first row (figure #9) to allow for irregularities.
- Install a starter board on the inside edge of the chalk line aligned to
create a straight edge to work against (figure8A). Attach the starter board
to the subfloor using nails appropriate to the subflooring materials. When
installing using the floating system install the cushion underlayment BEFORE
installing the starter strip.
FLOATING FLOOR INSTALLATION
STEP 2: INSTALLING THE UNDERLAYMENT
- Roll the underlayment in the same direction that the wood flooring is to
be installed.
- Extend the underlayment a few inches up the wall. Excess will be trimmed
off prior to installing trim or moldings.
- Firmly bond the sheets together to cover the entire floor. The floating
floor underlayment already has double sided tape for ease of taping the
precut overlapping seams (figure #7).

- Always allow ½" expansion around all vertical objects.
STEP 3: INSTALLING THE FLOOR
- Select your first board; apply a continuous 1/8" glue bead to the top
of the tongue on "the end of the board." Do not apply glue
to the side-tongue at this time (Item C, figure #8).
- Lay the first board (Item D, figure #8) with the grooves facing the edge
of the starter board and the left wall of the room. (Always leave expansion
space).

- Complete the first row. Cut the last board allowing for ½" clearance
between the wall and the floor. (Use the remaining end of the cut board
as a starter board for any row after row three). Use an installation
bar to pull the last board into place. Install wedges into the gap and
tighten (Item B, figure #8).
- If any glue gets on the surface of the flooring, wipe off immediately
with a damp cloth.
- Start the second row by applying a bead of SoundSeal adhesive along
the top side of the tongue of row one.
- Cut a board in half for the first board of the second row. Avoid installation
of any boards shorter than 25" in the first four rows which may
reduce the strength of the floor (Item F, figure #8).
- In the remaining rows, stagger joints at least 16" apart. When
installing boards together, use a tapping block against the tongue,
not the groove (Item G, figure #8). Apply a bead of SoundSeal to the
tongue on the end and side (Item C, figure #8). Tap the boards into
place by tapping with a hammer on the tapping block. DO NOT tap directly
on the boards with the hammer. Install the rest of the floor. Be sure
all joints are tight. Use spacers on the long and butt walls. Use an
installation bar to tighten the joints from the ends. Remove excess
adhesive with a damp towel.
- The final row of boards, in most installations, will need to be ripped
lengthwise to fit. The cut has to compensate for uneven walls and the
expansion clearance or gap necessary between the wall and the flooring.
First lay up the last row, face-up over the top of the last row permanently
installed. Now using a stub of a board and a pencil, scribe the proper
guide lines and cut (figure #9).
- Use an installation bar to pull in the last row (figure #10) and install
wedges.
- Remove the starter board and install the final row using the installation
bar as above.
- Allow the completed floor to rest undisturbed (no foot traffic) for
a minimum of 8 hours before removing the wedges.
- Before leaving the job site, check the floor under proper lighting for any
trace of glue on the surface. Use Robbins Adhesive Cleaner to remove
stubborn glue. Install molding the following day. Refer to the floor care
and maintenance section for maintaining your wood flooring.
scribe the proper guide lines and cut (figure #9).
Use an installation bar to pull in the last row (figure #10) and install wedges.
GLUE-DOWN INSTALLATION
- Maximum Adhesive Working Times
- FusionLock Urethane Adhesive - 60 minutes (Always read container label
before proceeding)
- ProConnectTM Adhesive - 60 minutes (Always read container
label before proceeding)
- Open times and curing times of ALL adhesives vary dependant upon subfloor
porosity, air movement, humidity and room temperature. Urethane adhesives
have a shortened work time in high humidity environments whereas resin
adhesive working time will be lengthened. In areas of low humidity,
open time will be longer with urethanes and shorter with resin adhesives.
Adjust the amount of adhesive spread accordingly. The adhesive should
not be applied if subfloor or room temperature is below 65° F (20° C).
- Spread sufficient amounts of FusionLock or ProConnectTM
adhesive (shown in header on page 1) with the recommended trowel (figure #2)
in an area that can be covered in 30-60 minutes. Resin adhesives should be
rolled every two hours and at the end of the day. If a urethane adhesive is
to be rolled, do not do so until the adhesive has cured for two hours.
NOTE: Avoid installing from the surface of the flooring. If
necessary distribute weight using a kneeler board. Always refer to specific
adhesive instructions on the adhesive label. PolyCusion underlayment will not be
used in this application.
STEP 2: SPREAD THE ADHESIVE
- Hold trowel at a minimum 45° angle (figure #11) firmly against the subfloor
to obtain a 50 sq. ft. per gallon spread rate. The trowel will leave
ridges of adhesive and very little adhesive between the ridges. This
will allow you to still see the chalk lines between the ridges and provide
the recommended spread rate. If the adhesive skins over and fails to
transfer, remove and spread new adhesive to achieve proper bonding to
the subfloor. WORKING TIME WILL VARY DEPENDING ON JOB SITE CONDITIONS.
- During the installation occasionally remove a piece of flooring from
the subfloor and inspect the back for proper adhesive transfer. Adequate
adhesive transfer is necessary to ensure sufficient holding strength.
- For additional application instructions, follow the recommendations
on the adhesive container.
- When not in use, keep the adhesive container tightly closed to prevent
thickening. Thickening will cause difficulty in spreading the adhesive.
- Proper ventilation within the room must be provided. An electric fan
is helpful.
- If the floor is to be covered, use a breathable material such as
cardboard. Do not cover with plastic.
NOTE: Clean adhesive from the surface of the floor
frequently using the recommended adhesive cleaner. Do not use blue tape before
adhesive is removed. Use a clean towel, changed frequently to prevent haze and
adhesive residue.
STEP 3: INSTALLATION OF FLOORING
- Use the straightest boards available for the first two rows. The first row
of planks should be installed with the edge of the groove lined up against
the starter board. The tongue should be facing the starting wall. The
first row must be aligned and seated in the adhesive as all additional
rows will be pushed back to this original row.
- Apply a bead of SoundSeal to all of the end tongues prior to installing
into the adhesive. Gluing of the edges is not necessary in glue-down
applications.
- Use wedges against the starting wall to prevent movement. Tighten
or loosen as necessary to allow for variations in the wall, always keeping
planks aligned with the chalk line.
- Avoid working from the surface of the newly installed floor to prevent
scooting. Use a kneeler board if necessary to distribute weight.
- When installing planks, engage the end-joint first as close to the
side (long) tongue and groove as possible and then slide together tightly
to engage side (long) joint tongue and groove. To avoid adhesive bleed-through
and memory pull-back, avoid sliding pieces through the adhesive as much
as possible when placing them in position.
- Check for a tight fit between all edges and ends of each plank. End-joints
of adjacent rows should be staggered 16" when possible to ensure
a more favorable overall appearance.
- Use a glue-down tapping block and a hammer to tighten all joints.
- To eliminate minor shifting or gapping of product during installation,
use 3M 2090 Blue Mask Tape to hold the planks together. After installation
is complete, remove all the 3M 2090 Blue Mask Tape from surface of newly
installed flooring. Do not let tape remain on flooring longer than 24
hours. Avoid use of masking tape which leaves an adhesive residue.
- Be sure not to spread adhesive too far ahead of your work area.
- Complete the installation using this same technique for the remainder
of the floor.
- Remove the starter board and install the final row as above.
- Avoid heavy foot traffic on the flooring for at least 24 hours. Lift the
furniture or fixtures back into place after 24 hours.
INSTALLERS - ADVISE YOUR CUSTOMER OF THE FOLLOWING
SEASONS: HEATING AND NON-HEATING
Recognizing that wood floor dimensions will be slightly affected by varying
levels of humidity within your building, care should be taken to control
humidity levels within the 35-55% range. To protect your investment and to
assure that your floors provide lasting satisfaction, we have provided our
recommendations below.
- Heating Season (Dry) - A humidifier is recommended to prevent
excessive shrinkage in wood floors due to low humidity levels. Wood
stoves and electric heat tend to create very dry conditions.
- Non-Heating Season (Humid, Wet) - Proper humidity levels
can be maintained by use of an air conditioner, dehumidifier, or by turning
on your heating system periodically during the summer months. Avoid
excessive exposure to water from tracking during periods of inclement
weather. Do not obstruct in any way the expansion joint around the perimeter
of your floor.
FLOOR REPAIR
Minor damage can be repaired with Robbins Touch-Up Kit or Acrylic Filler. Major
damage will require board replacement, which can be done by a professional floor
installer.
ALL INSTALLATIONS
STEP 4: COMPLETING THE JOB
- Clean floor with the Robbins ForEver II Hardwood Flooring Cleaner. (See
adhesive container for specific information)
- Re-install any transition pieces that may be needed, such as Reducer
Strips, T-moldings, or Thresholds. The products are available pre-finished
to blend with your flooring. (See moldings below)
- Re-install all base and/or quarter round moldings. Nail moldings into
the wall, not the floor. Inspect the floor, filling all minor gaps with
the appropriate blended filler.
- If the floor is to be covered, use a breathable material such as cardboard.
Do not cover with plastic.
- Leave warranty and floor care information with the owner. Advise them
of the product name and code number of the flooring they purchased.
- To prevent surface damage avoid rolling heavy appliances and furniture on
the floor. Use plywood, hardboard or appliance lifts if necessary.
MOLDINGS
- Reducer Strip: a teardrop shaped molding. Used around fireplaces,
doorways, as a room divider, or as a transition between Parquet and
adjacent floor coverings that are less thick. Fasten down with adhesive
or double-faced tape.
- Threshold: a molding undercut for use against sliding
door tracks, fireplaces, carpet, ceramic tile, or existing thresholds
to allow for expansion space and to provide a smooth transition in height
difference. Fasten to subfloor with adhesive and/or nails through the
heel. Predrill nail holes to prevent splitting. Always leave expansion
beneath the undercut.
- Stair Nosing: a molding undercut for use as a stair
landings trim, elevated floor perimeters, and stair steps. Fasten down
firmly with adhesive and nails or screws. Predrill nail holes to prevent
splitting.
- Quarter Round: a molding used to cover expansion
space next to baseboards, case goods, and stair steps. Predrill and
nail to the vertical surface, not into the floor.
- Combination Base and Shoe: a molding used when a
base is desired. Used to cover expansion space between the floor and
the wall. Predrill and nail into the wall, not the floor.
- T-Molding: a molding used as a transition piece from one
flooring to another or to gain expansion spaces. Fasten at the heel in the
center of the molding. Leave expansion beneath the undercut on both sides.